Controller performance assessment at the presence of complex distrubances
Ein modellbasiertes Benchmark-Verfahren
DOI:
https://doi.org/10.17560/atp.v61i4.2392Keywords:
Controller performance assessment, H2-optimal control, Control performance indexAbstract
A method for performance assessment of a control loop at the presence of combined deterministic-stochastic disturbances is presented. The deterministic component of a process disturbance is described with the help of the appropriate model, e.g. transfer function, in order to set up the required H2-optimal benchmark. The stochastic disturbance component is modelled separately and the stochastic part of the system behavior is evaluated additionally with the help of the conventional minimum variance control benchmark. A performance of a control system is assessed hereby based on the L2-norm of the system output or the control error.
Downloads
Published
Issue
Section
License
Die Zeitschrift und alle in ihr enthaltenen Beiträge und Abbildungen sind urheberrechtlich geschützt. Jede Verwertung außerhalb der engen Grenzen des Urheberrechtsgesetzes ist ohne Zustimmung des Verlages unzulässig und strafbar. Das gilt insbesondere für Vervielfältigungen, Übersetzungen, Mikroverfilmungen und die Einspeicherung und Bearbeitung in elektronischen Systemen. Auch die Rechte der Wiedergabe durch Vortrag, Funk- und Fernsehsendung, im Magnettonverfahren oder ähnlichem Wege bleiben vorbehalten.